Calorimetric flow switch FS 10 is produce with 1× status output (depending on flow velocity).
It is a device that monitors the flow of fluid based on calorimetry principle. If the flow rate drops below a limit set by user, the status output is changed. The flow rate is displayed by ten LEDs and it is possible to select a boundary for contact making/breaking in the same graduation. The measuring cycle takes from 4 sec to 8 sec with the recommended measurement range 4 ÷ 150 cm/sec. In case of an empty pipeline, the sensor behaves in the same way as with zero flow.
Meter states displayed
The flow switch point on LED scale can be implemented using two colours (red LED or amber LED), indicating at the same time which contact is normally closed or normally, open. In case of FS15, the temperature switch point is indicated by the LED located between the control push buttons. If the temperature of media is above/below the set-point, the LED is red, indicating that PIN2 is open at the same time (the sensor supplied as standard is configured open at a temperature above the set limit with the LED turned ON). If the logic of the normally open/normally closed point is changed by the user, the logic of both outputs is changed at the same time (applicable to FS 11 and FS15 versions).
The flow switch has two flush-type control buttons, making it possible:
- the switching point/points for flow velocity (temperature in some case)
- to change the logic of the N.O./N.C. output
- to calibrate the minimum and maximum flow values of the monitoring device
- to reset the original parameters from factory
ACCESSORIES
- FS Adapter block
- SPECIFICATIONS
- DIMENSIONAL DRAFT
- WIRING DIAGRAM
- DOWNLOAD
Type sensor | FS 10 |
Power supply | 24 V ± 10%DC with polarity reversal protection |
Input power | 1.5/4 VA |
Electrical connection | connector M12x1 (4PIN) |
Process connection | according to DIN2353 with the M16 × 1,5 union nut through the 24° ring into the direct socket with pipe thread (G1/2“; G1/4“; M14 × 1.5; NPT1/4“) |
Sensor design | compact, separated (standard 3 m cable) |
Display | 10× three-colour LED (flow velocity) |
1× LED (temperature – for FS 15 only) | |
Output types relay | relay (for FS 10), PNP, NPN, 4 to 20 mA (for FS 20 only) |
Contact rating | 130 mA / 60 V / 500 mW |
Response time* | 1 to 6 s |
Velocity flow range | 4 to 400 cm/s |
Accuracy | ±2 to ±8 cm/s |
Hysteresis | 2 to 8 cm/s |
Control | 2 × flush-mounted button |
Temperature of liquid | -10 to 80 °C |
Ambient temperature | -20 to 55 °C |
Material in contact with medium | stainless steel DIN 1.4404 |
Maximum pressure | 64 bar |
Degree of protection | IP 67, in accordance with EN 60529, as amended |
Ambient humidity | max. 90 % |
Status contact | SSR, passive, potential free, max. 350 V |
AC/DC, 150 mA, 400 mW | |
Weight | 290 g |
Dimensions (h×w×d) | 91 × 74 × 60 mm (in case of the longer version, the height is 151 mm) |