WRU90001 is a wireless, battery powered HMI unit. The device features temperature, humidity and CO2 sensors, the values of which can be displayed to user on a large LCD display. It features a native modbus map that grants seamless integration into the DDC/SCADA system. The communication is based on the encrypted Midam KFP protocol, which allows to update the device firmware on a wireless basis.
APPLICATION
- HVAC control
- measurement of temperature, humidity and CO2
- display of status values
- wireless integration into SCADA control systems
FUNCTION
The wireless room unit measures temperature and relative humidity. It allows to set the desired temperature setpoint and operating modes using the rotating knob. The values are transmitted through the 868 MHz unlicensed band to the WCOM51 gateway. There is also an option without rotationg know and display available. The room unit features a native modbus map with the direct read and write functionality. The modbus map is available in a separate document. All settings and configuration are also stored in a modbus register, directly in the device. It is necessary to pair the device before first use and to enter the encryption password.
Modbus protocol for WRU90001 for downloading HERE.
SCADA system integration
The controller can be integrated into DDC or SCADA systems directly via the WCOM51 wireless gateway.
PAIRING
To pair your own sensors with the WCOM51 GSM gateway, the freely downloadable KFP-Lite software is available, which communicates with the gateway using the WUSB01 wireless USB configurator. Both devices must be powered and placed in close proximity to each other. Using the search function in the software interface, you can view a list of all available devices in range and assign or modify parameters based on the wireless identification code for each individual device.
Using KFP-Lite, it is possible to change the communication frequency (default value 868.95 MHz).
DOWNLOAD KFP-LITE FOR FREE HERE.
BATTERY CHANGE
Remove the base lid of the controller by gently pressing it on the sides. Remove old batteries from the bracket and place new batteries. Observe the battery type and polarity. Always replace both bateries with fresh ones. Then put both parts together and close the controller again.
- SPECIFICATIONS
- DIMENSIONAL DRAFT
- WIRING DIAGRAM
- DOWNLOAD
Wireless room unit | WRU90001 |
Power supply | 4,5V, 3× main alkaline battery 1,5V, type AA |
Consumption | Idle: <10 uA, avg. typical: 90 uA, max.: 25 mA |
Battery life | up to 3 years – batteries are not supplied with the device |
Communication | 868,950 MHz, 100 kbps, WMBUS T1, KFP 868,300 MHz, 32 kbps, WMBUS S1, KFP 868,100 MHz, 100 kbps, KFP 869,525 MHz, 100 kbps, WMBUS C, KFP 868,300 MHz, 38 kbps, KFP |
Protocol | WMBUS (EN 13757-4), KFP (dual stack) |
Encryption | AES 128 PCBC, EN 13757-4 |
RF power | +10 až - 20 dBm, krok 5 dB |
Antenna | Integrated |
Communication range | 100 m in free space, 30 m in buildings |
Mechanical and dimensions | 90×115×30 mm enclosure ABS, IP 20 in accordance with EN 60529, as amended 2 × DIP switch (INIT mode, USR mode) |
Temperature measurement range | -20 to 55 °C, ± 0,5 °C |
Humidity measuring range | 10 až 90 % rH, ±3% rH |
CO2 measuring range | 400 to 5000 ppm (secondary output 0-100%) |
CO2 measuring method | NDIR (Non-dispersive Infra Red) |
CO2 measuring accuracy | ± 30ppm, ± 3% of measured value (defined conditions for at least 3 calibration ACDL completed over the past 3 weeks). ACDL (automatic calibration in dimming light mode). |
Temperature setpoint | configurable, ± 10 to ± 1 K |
Display | reflexive segmented LCD 60×60 mm |
Ambient conditions | -5 to 45 °C, 5 % to 95 % rH (EN 60721-3-3 class 3K5) |
Note: Manufacturer reserves the right to make changes in design and technical characteristics of the products. For actual information, please always contact your dealer.